Special characteristics
Nominal sizes
Filter classes
Construction
Frame versions made from extruded aluminium sections
List of frame depths according to construction:
Profiles for continuous seal/flat seal
Filter class | Upstream velocity | Pleat depth | ||||||||
DIN EN ISO 16890/ DIN EN 1822 | 20* | 46 | 50 | 58 | 68 | 70 | 73 | 90 | 120 | |
ePM10 55 % | 2.57 m/s | 90 Pa | ||||||||
ePM1 65 % | 2.57 m/s | 110 Pa | ||||||||
ePM1 90 % | 2.57 m/s | 150 Pa | ||||||||
E11 | 0.90 m/s | 125 Pa | 135 Pa | 125 Pa | ||||||
H13 | 0.90 m/s | 250 Pa | 270 Pa | 250 Pa | 215 Pa | 195 Pa | 135 Pa | |||
H14 | 0.45 m/s | 115 Pa | 110 Pa | 95 Pa | 90 Pa | 85 Pa | 80 Pa | 75 Pa | 70 Pa | |
U15 | 0.45 m/s | 130 Pa | 115 Pa | 105 Pa | 100 Pa | 95 Pa | 80 Pa | |||
U16 | 0.45 m/s | 140 Pa | 125 Pa | 120 Pa | 115 Pa | 105 Pa | ||||
* When the pleat depth depth is 20 mm, the face velocity is 0.45 m/s.
The initial differential pressure [Pa] depends on the filter class and the pleat depth.
The nominal volume rate is the product of the corresponding face velocity and the filter face area (B x H), minus the profile thickness. See chapter Quick sizing.
Specification text
Areas of application:
Design and construction:
Versions and filter groups:
Sealing systems and options:
Test:
Special features
Materials and surfaces
Construction
Profiles with groove for continuous seal:
Profiles for continuous seal/flat seal
Profiles with knife edge profile
Sizing data
| MFPCR | – | H14 | – | – | ALC | – | R | / | 1220 × 610 × 78 × | 58 | / | PD | / | CSD | – | 11 | – | / | ST | / | LFD | ||
| | | | | | | | | | | | | | | | | | | | | | | | | | | |||||||||||
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 |
2 Filter class
ePM1 Fractional efficiency ePM1 according to DIN EN ISO 16890
ePM10 Fractional efficiency ePM10 according to DIN EN ISO 16890
E11 Filter class E11 according to DIN EN 1822
H13 Filter class H13 according to DIN EN 1822
H14 Filter class H14 according to DIN EN 1822
U15 Filter class U15 according to DIN EN 1822#
U16 Filter class U16 according to DIN EN 1822
3 Separation efficiency
Only with filter class ePM1, ePM10
Specify separation efficiency [%] according to DIN EN ISO 16890
4 Construction
Extruded aluminium section
ALN smooth frame for flat seal (depth 30 mm)
ALZ smooth frame for flat seal (depth 78 mm)
ALY smooth frame for flat seal (depth 150 mm)
ALD Frame with groove for foamed seal (depth 66 mm)
ALB Frame with groove for foamed seal (depth 69 mm)
ALC Frame with groove for foamed seal (depth 78 mm)
ALG Frame with groove for foamed seal (depth 90 mm)
ALV Frame with U-profile for fluid seal (depth 85 mm)
ALU Frame with U-profile for fluid seal (depth 91 mm)
ALQ Frame with U-profile for fluid seal (depth 105 mm)
ALT Frame with U-profile for fluid seal (depth 130 mm)
ALL Frame with knife edge profile (depth 94 mm)
ALS Frame with knife edge profile (depth 105 mm)
ALR Frame with knife edge profile (depth 109 mm)
ALX Frame with knife edge profile (depth 134 mm)
5 Section upstream side
No entry: Standard
R reverse execution (not with ALV, ALU, ALQ variant)
6 Nominal size [mm]
Specify width × height × depth
7 Pleat depth [mm]
Specify pleat depth
8 Protection grid
No entry: without protection grid
PU Protection grid on the upstream side
PD Protection grid on the downstream side
PB Protection grid on both sides
9 Seal
WS without seal
FNU Flat seal on the upstream side
FND Flat seal on the downstream side
FNB Flat seal on both sides
TGU Test groove seal on the upstream side
CSU Continuous seal on the upstream side
CSD Continuous seal on the downstream side
CSB Continuous seal on both sides
GPU Fluid seal (only with ALV, ALU, ALQ, ALT version)
10 Seal type upstream side
Only with seal FNU, FNB, TGU, CSU, CSB, GPU
Specify seal type
11 Seal type downstream side
Only with seal FND, FNB, CSD, CSB
Specify seal type
12 Tests
No entry: no leakage test
OT Oil mist test (filter classes H13 and H14 only)
OTC Oil mist test with certificate (filter classes H13 and H14 only)
ST Scan test (filter classes H13, H14, U15, U16 only)
13 Laminating
No entry: no lamination
LFU full-surface laminar fleece, upstream side
LFD full-surface laminar fleece, downstream side
LFS Laminar fleece strips
Order example: MFPCR-H14-ALC-R/1220×610×78×58/PD/CSD-11/ST/LFD
| Type | MFPCR - Mini Pleat filter panel for clean room technology |
| Filter class | Filter class H14 according to DIN EN 1822 |
| Separation efficiency | - |
| Construction | Frame with groove for foamed seal (depth 78 mm) |
| Section upstream side | reverse execution |
| Nominal size [mm] | Width 1220, height 610, depth 78 |
| Pleat depth [mm] | 58 |
| Protection grid | Protection grid on the downstream side |
| Seal | Continuous seal on the downstream side |
| Seal type upstream side | - |
| Seal type downstream side | Continuous seal foamed in groove |
| Testing | Scan test |
| Laminar distribution fleece | full-surface laminar fleece, downstream side |
Podeli stranicu
Preporuči ovu stranicu
Preporuči ovu stranicu slanjem linka putem email poruke.
Podeli stranicu
Zahvaljujemo se na Vašoj preporuci!
Vaša preporuka je poslata i biće uskoro isporučena.
Kontakt
Tu smo za vas
Molimo Vas da navedete sadržinu poruke i vrstu zahteva
Tel.: +381 11 2622 543 | Fax: +49 (0)2845/202-265
Kontakt
Zahvaljujemo na vašoj poruci!
Vaša poruka je poslata i biće uskoro obrađena.
Naše odeljenje za servisnu podršku će Vas kontaktirati u najkraćem roku.
Za opšta pitanja u vezi proizvoda ili usluga možete takoše da pozovete:
Tel.: +381 11 2622 543 | Fax: +381 11 2624 150
Kontakt
Tu smo za vas
Molimo Vas da navedete sadržinu poruke i vrstu zahteva
Tel.: +381 11 2622 543 | Fax: +49 (0)2845/202-265
Kontakt
Zahvaljujemo na vašoj poruci!
Vaša poruka je poslata i biće uskoro obrađena.
Naše odeljenje za servisnu podršku će Vas kontaktirati u najkraćem roku.
Za opšta pitanja u vezi proizvoda ili usluga možete takoše da pozovete:
Tel.: +381 11 2622 543 | Fax: +381 11 2624 150