X-CUBE SCHOOLAIR-D-HV-EH       

Supply and extract air unit with electric air heater and rotary heat recovery unit, secondary air option, for installation below the ceiling slab

Ready-to-operate decentralised ventilation unit that provides good comfort levels and is used for the ventilation of internal spaces such as classrooms or conference rooms and day nurseries
■ Freely suspended installation or partially or fully integrated in a suspended ceiling
■ Acoustically optimised EC fans with low specific fan power, SFP = 0 to EN 16798-3
■ Rotary heat recovery unit (75% heat recovery efficiency) with moisture recovery in winter
■ Electric air heater with 3000 W max. heating capacity
■ Heat recovery all year round
■ Reduced fine dust and pollen contamination due to integral filters that conform to VDI 6022 – filter class ISO ePM1 60% and extract air ISO coarse 90%
■ Easy filter change, no tools required
■ Motorised shut-off dampers, normally closed (NC)
■ Installation without interruption of school operations

Optional equipment and accessories
■ Modular control system FSL-CONTROL III, specially for decentralised ventilation systems

Tehničke informacije

  • FUNCTION
  • TECHNICAL DATA
  • QUICK SIZING
  • SPECIFICATION TEXT
  • ORDER CODE

Functional description

Decentralised supply and extract air units for room ventilation and for dissipating heat loads. An EC centrifugal fan takes in the outdoor air which then flows through the motorised shut-off damper and the outdoor air filter. The outdoor air then flows through the rotary heat recovery unit, which can be switched off if it is more energy efficient. If necessary, the air is heated by the electric air heater before it is discharged through the supply air grille towards the ceiling (Coanda effect) with a high propulsive force, yet without creating a draught. The extract air first passes the extract air filter, then flows through the heat recovery unit, the extract air fan and the motorised shutoff damper before it is discharged to the outside as exhaust air. If the indoor air quality is sufficient, FSL-CONTROL III closes the outdoor air dampers and changes to secondary air operation, which is more energy efficient in any case. The control system compares the room air quality setpoint value to the actual value measured by the CO2 sensor and switches automatically between outdoor air and secondary air operation. If the power fails, the outdoor air and exhaust air dampers are closed to ensure fire protection and frost protection and to avoid draughts. This is ensured by a capacitor in each actuator. The supply air is discharged near the ceiling with a medium velocity. Rather than flowing immediately downwards, the air moves along the ceiling (Coanda effect) and reaches every corner; this ensures complete ventilation even of large rooms. Once the air reaches the opposite wall, it moves downwards and eventually through the entire space. The airflow reaching the occupied zone has a very low velocity and rises on heat sources, for example on people and devices. This is called natural convection. As a result, the air is exchanged primarily in these areas. The stale air is extracted under the ceiling and led to the outside.

Width

3363 mm, 3555 mm, 3905 mm, 3900 mm

Height

410 mm, 440 mm

Depth

1030 mm, 1099 mm

Volume flow rate

300, 500, 800 m³/h (boost 1100 m³/h)

Nominal volume flow rate

800 m³/h

Sound pressure level at nominal volume flow rate and 8 dB

Room attenuation

35 dB(A)

Sound power level

22 – 53 dB(A)

Degree of heat recovery efficiency

75 %

Supply voltage

230 V AC ±10 %, 50/60 Hz

Connected load (depending on the electric heating coil

1200/1800/2400/3000 W)

1880/2480/3080/3680 VA

Weight

340 kg

SCHOOLAIR-V-HV (example of 2-pipe construction – active heating)

Supply air volume flow

m³/h

300

500

800

1100

Sound power level LWA

dB(A)

22

34

43

53

Sound pressure level including 8 dB system attenuation

dB(A)

14

26

35

45

Active power Pel

W

30

65

150

315

This specification text describes the general properties of the product. Texts for variants can be generated with our Easy Product Finder design program.

X-CUBE/SCHOOLAIR-D-HV-0-EH/3363×410×1030/0/C3
Decentralised ventilation unit for ceiling installation
Please note:
The ceiling ventilation unit variant described is equipped with an integrated individual room control for independent classroom operation.
The supplied controllers contain the parameters of the standard control for operation according to our control description Ventilation unit for schools – ceiling installation – master unit
Ventilation unit for ceiling installation TROX X-CUBE/ SCHOOLAIR-D-HV-0-EH with supply and extract air function, rotary heat recovery unit and switchover option to secondary air operation (air quality dependent), as well as electric reheating function:
  • Just one unit fulfills the increased fresh air requirement for an entire classroom
  • Equipped for installation in a suspended ceiling in one level, flush with the bottom edge of the unit
  • 2-part casing made of galvanised sheet steel, all internal ducts are sealed and insulated, internal electric cable penetrations are sealed, exposed surfaces are powdercoated (RAL 9010, GU 20; alternatively RAL 7012, GU 20)
  • Intake and discharge sides with noise and heat insulation made of mineral wool faced with glass fibre scrim (fire rating class A, non-combustible according to DIN 4102, part 1), erosion resistant up to air velocities of 20 m/s, or closed cell insulation material (fire rating class B)
  • The unit meets the hygiene requirements of VDI 6022
  • Interior fixing points and unique 2-part casing simplify ceiling installation
  • Connection to the on-site outdoor air and exhaust air openings (provided by the client) in the wall at the back of the unit, with perimeter closed-cell sealing tape, d=10 mm (the intake and outlet resistance of the construction provided by others should not exceed 40 Pa at the nominal volume flow rate), alternatively with duct connections
  • Extract air intake opposite the supply air intake, including extract grille
  • Room supply air discharge at the bottom of the unit through innovative supply air diffuser with guaranteed room ventilation, regardless of whether mounted above the blackboard (front side) or on the façade side
  • The inspection access panels are hinged on one side and fitted with special fasteners to facilitate maintenance. The underside of the unit it has to be freely accessible for maintenance or possible deinstallation
  • Use of 2 free-running wheels with backward-curved blades, energy-saving EC technology, supply and extract air fan classified in category SFP 0 (< 300 W/(m³/s)) in accordance with DIN EN 16798-3:2017-11. A connected load of 3680 VA must be taken into account when dimensioning the connecting cable
  • Suitable for 3 speed levels (300, 500 and 800 m³/h as well as boost level of 1100 m³/h), signalling by means of integrated single room control system. The volume flow rate can be corrected at a later stage by adjusting the control voltage
  • Sound attenuators on the upstream and downstream sides provide maximum reduction of sound power levels
  • The technical requirements of EU directive 1253/2014 for non-residential ventilation systems are fulfilled and documented in accordance with the directive
  • Integrated rotary heat exchanger for heat recovery, with high heat recovery efficiency (> 75%), modulating control by integral single room control system
  • Motorised shut-off dampers in the outdoor air and exhaust air ducts, normally closed when there is no power (via energy storage), 230 V open/close actuator, signalling with integrated single room control system
  • Automatic switching to secondary air mode (only with an air quality sensor) if the room air quality (measured with the integral CO2sensor) is within the defined limits. The outdoor air damper closes, the secondary air damper opens and the extract air fan is switched off.
  • Integral electrical components are completely wired with FSL-CONTROL III, control components are integrated in the unit. Cable for connection (connection by others) to the power supply (L, N, PE), with wire end ferrules, approx. 1 m routed out of the casing. As a transfer point to the existing electrical system:
    • Supply voltage (230 V): 3 wires, 3 × 1.5 mm² (L, N, PE)
  • Connection option for bus communication (optional), connection of room control panel etc. after opening the customer area of the control unit. As a transfer point to the on-site measurement/control/regulation system:
    • Rail mount terminals type Wago 260 for the on-site connection of
      • Digital inputs DI
      • Digital outputs DO
      • Master-slave connection RS485
      • Optional integration into MCE/BACS via RS485 (Modbus/BACnet)
      • Control panel
      • RJ45 socket as service access to the user interface
      • Optional integration into an on-site MCE/BACS via Ethernet (Modbus/BACnet)
  • The following sensors are included in the unit as part of the single room control system (the actual room temperature is captured at the room control panel):
    • Room air quality sensor CO2
    • Supply air temperature measurement downstream of the heat exchanger
    • Outdoor air temperature measurement in the outdoor air intake
  • The outdoor air filter is a pocket filter with non-woven glass fibre, ISO ePM1 (fine dust filter):
    • Filter class as per ISO 16890: ISO ePM1 60%
    • Eurovent Certification for fine dust filters
    • Meets the hygiene requirements of VDI 6022
    • High energy efficiency class according to Eurovent
    • Glass fibre nonwovens, in sewn design
    • Enlarged filter area due to filter pockets
    • Low initial differential pressure and high dust holding capacity, ideal airflow conditions due to wedgeshaped filter pockets
    • Quick installation and filter changes thanks to easy and safe handling
    • Filter area ≥ 1.4 m²
  • Extract air filter with large filter surface due to pleated filter media
    • Filter class as per ISO 16890: ISO Coarse 90%
    • Low differential pressures at high volume flows
    • Filter media made of synthetic fibres
    • Moisture-resistant frame made of non-woven fabric
    • Tested as per ISO 16890
  • Quick filter change as the filter chamber is immediately accessible once the cover has been opened
  • Differential pressure measurement for filter monitoring, evaluation via integrated single room control system
  • The heat exchanger is an electric air heater
    • Maximum heating capacity according to the version shown in the order code:
      • EH-30: 3000 W, continuously controlled
      • EH-24: 2400 W, continuously controlled
      • EH-18: 1800 W, continuously controlled
      • EH-12: 1200 W, continuously controlled
      • The surface temperature does not exceed 60 °C to safely prevent the smouldering of dust
  • Including control loop, consisting of temperature sensor, NTC 10 kΩ, and power controller
  • Supply air temperature: 25 °C max.
  • Including safeguards:
    • Safety temperature limiter, mechanical, automatically resetting
    • Safety temperature monitor, mechanical, no auto reset

Devices - dimensions and weight:

Width: approx. 3363 mm (without fixing brackets)

Height: approx. 410 mm

Depth: approx. 1030 mm (without façade seals)

Weight: approx. 340 kg

FSL-CONTROL III controller
  • Self-sufficient single-room control with simple time programme
Optional expansions for FSL-CONTROL III:
  • Humidity sensor Return temperature sensor
  • Electric valve actuators
  • Pressure-independent control valves
  • Integration into an on-site MCE/BACS via:
    • Modbus TCP
    • Modbus RTU
    • BACnet MS/TP
    • BACnet IP

Note:

The optional expansions are included in the delivery programme, but must be exchanged for the standard components in the following description.

  • A room temperature signal is required
  • Various room control panels and a room temperature sensor are available
  • Associated optional equipment options - see Optional control accessories.
  • We recommend commissioning by TROX.

TROX control module FSL-CONTROL III (order code ...-C3- MA ...):
  • Single room controller to be mounted on a DIN mounting rail in the device or in a separate control casing
  • 42 digital or analogue inputs and outputs
  • Integrated microSD card as flash memory medium
    • At least 2 GB storage space
    • Saves the trend data
    • Retrievable via RJ45 connection socket
  • Factory-equipped with a software package for master units specially developed for decentralised ventilation units.
    • For simple master-slave communication via Modbus RTU
  • Up to 10 slave devices can be connected to one master device
  • Software:
    • 3 operating modes: Off, Automatic, Manual mode
    • 3 operating modes: Occupied, Unoccupied, Standby
    • 4 operating mode overrides: Boost, closed circuit, night purge, fan forced circuit
  • Basic distinction between room temperature control by controlling heating and cooling valves or continuous bypass damper, or supply air temperature control for isothermal ventilation operation
  • CO2-guided air quality control
  • Heat recovery all year round
  • Filter monitoring
  • Configurable DI for on-site connection of presence detectors, window contacts, holiday switching, etc.
  • Alarm messages: Type A (shutdowns) and Type B (notifications)

Real time clock (RTC)
Real Time Clock (RTC/real time clock) (order code ...-T/...):
  • Component of the Master Software Package
  • Enables a simple timer
    • 7 days with 10 switching points each
    • Automatic summer / winter time changeover
    • Temporal activation of night purge

CO2 sensor
CO22sensor (order code…/C/…):

  • Sensor arranged in the extract air intake of the master unit for recording the indoor air quality and corresponding control of the outdoor air flow rate
  • Measurement via an NDIR sensor, which works on an infrared basis and compensates for any contamination by its 2-beam measurement principle
  • Measuring range 0 – 2000 ppm

Supply air temperature sensor

Supply air temperature sensor (order code .../Z/...):

  • Supply air temperature sensor with NTC thermistor, 10 kΩ at 25 °C, measuring range -35 to 105 °C
  • Very short response time due to perforated measuring tip

Outdoor air temperature sensor

Outdoor air temperature sensor (order code .../A/...):

  • Outdoor air temperature sensor with NTC thermistor, 10 kΩ at 25 °C, measuring range -35 to 105 °C

Optional control accessories

Optional equipment to increase the comfort of the FSLCONTROL III:

TROX room control panels for FSL-CONTROL III

At least one room temperature signal is required per room. There are several variants of TROX room control panels available, optionally with or without selector switch. Additionally, we offer a room temperature sensor RTF without control elements. Alternative on-site room control panels must be connected via bus communication.

Digital room control panels for surface mounting:

For operation and adjustment of the ventilation units.

  • Supplied loose as an accessory. Connection to the master unit via Modbus serial line. Project-specific software including setpoint value adjuster, various status displays, selector switch, CO2 indicator. Touch-sensitive colour display 3.5" 320 × 240 pixels. Sensor: NTC 10 kΩ. Degree of protection: IP 20. Type: Schneider TM172DCLWT. Dimensions (H × B × T): 120 × 86 × 25 mm. Weight: 340 g, colour: white. Installation: Surface mounting or on a standard flush-mounted box. Power supply: 24 V DC (including suitable switching power supply unit for flushmounted installation). Power consumption: 3.2 VA/1.3 W. Other design frames are available upon request and for a surcharge.

Control panels with selector switch for surface mounting:

Control panel with selector switch, for surface mounting, type Thermokon

  • Supplied loose as an accessory, with room temperature sensor, setpoint adjuster, override button, LED and 3-step switch as well as Off and Automatic, casing made of PVC0, pure white (RAL 9010), for mounting on a 60 mm flush box or for surface mounting, NTC thermistor as sensor, resistance 20 kΩ at 25 °C, dimensions (B × H × T): 84.5 x 84.5 x 25 mm, operating temperature: -35 to 70 °C

Control panels without selector switch for surface mounting:


Control panel without selector switch, type Thermokon, for surface mounting:

  • Supplied loose as an accessory, with mode display, push button and setpoint adjuster, NTC thermistor as sensor, 20 kΩ, protection level IP 20, dimensions (B × H × T): 84.5 x 84.5 x 25 mm

Room temperature sensor for surface mounting:


Room temperature sensor TROX RTF, surface mounting

  • Supplied loose as an accessory, room temperature sensor without any control elements, measuring range -35 to 70 °C, sensor NTC 10 kΩ, connection terminal screw terminal, d = 1.5 mm, protection level IP 20, surface mounting or on a 70 mm flush-mounted box, dimensions (B × H × T): 85 x 85 x 30 mm, casing ABS, in RAL 9010

Control panels without selector switch for flush mounting:

For manual operation of the ventilation units with a high-quality look and the matching design from a wide range of switch programmes, the unit is suitable for particularly design-oriented facilities.

Control panel without selector switch, type Thermokon, for flush mounting, switch from Berker S.1 range, polar white

  • Supplied loose as an accessory, with mode display, push button and setpoint adjuster, NTC sensor 20 kΩ, protection level: IP 20

Control panel without selector switch, type Thermokon, for flush mounting, switch programme Berker Q.3, white

  • Supplied loose as an accessory, with mode display, push button and setpoint adjuster, NTC sensor 20 kΩ, protection level: IP 20

Control panel without selector switch, type Thermokon, for flush mounting, switch programme Busch-Jäger future® linear, white

  • Supplied loose as an accessory, with mode display, push button and setpoint adjuster, NTC sensor 20 kΩ, protection level: IP 20
  • Other switch programmes on request

Control panels without selector switch and without setpoint value adjuster, for flush mounting:

Control panel without selector switch and without setpoint value adjuster, type Thermokon, for flush mounting, switch from Gira E2 range

  • Supplied loose as an accessory, with mode display and push button, NTC sensor 20 kΩ, protection level: IP 20
  • Other switch programmes on request

Interface for integration into an on-site MCE/BACS:

Modbus TCP interface including web server (order code .../ MT/...)

To increase convenience, we recommend integration into an onsite MCE/BACS or visualisation with X-TAIRMINAL. FSLCONTROL III can be integrated into an on-site MCE/BACS via the Modbus TCP protocol. Additionally including web server for simplified configuration, commissioning and remote monitoring of the unit. The MCE/BACS is not included in the supply package from TROX GmbH, only the interfaces listed above are available here.

  • Modbus TCP interface (Ethernet)


BACnet IP interface including web server (order code .../BI/...)

To increase convenience, we recommend integration into an onsite MCE/BACS. FSL-CONTROL III offers the option of being integrated into an on-site MCE/BACS via the BACnet IP protocol. Additionally including web server for simplified configuration, commissioning and remote monitoring of the unit. The MCE/ BACS is not included in the supply package from TROX GmbH, only the interfaces listed above are available here.

  • BACnet IP interface (Ethernet)

Modbus RTU (order code .../MR/...)

To increase convenience, we recommend integration into an onsite MCE/BACS. FSL-CONTROL III offers the option of being integrated into an on-site MCE/BACS via Modbus RTU. The MCE/BACS is not included in the supply package from TROX GmbH, only the interfaces listed above are available here.

  • Modbus RTU interface (RS485)

BACnet MS/TP (order code .../BM/...)

To increase convenience, we recommend integration into an onsite MCE/BACS. FSL-CONTROL III offers the option of being integrated into an on-site MCE/BACS via BACnet MS/TP. The MCE/BACS is not included in the supply package from TROX GmbH, only the interfaces listed above are available here.

  • BACnet MS/TP interface (RS485)

Version as a slave device
Identical to the master device, as described above, but with the following deviations:
  • No room air quality measurement in the unit
  • No connection option for room control panels
  • No outdoor temperature detection in the outdoor air
  • No connection to on-site bus communication possible
  • Pre-assembled self-sufficient control system for decentralised façade ventilation units in slave version

Replacement filter set suitable for the appliance version

  • Extract air filter as Z-Line filter
  • Outdoor air filter as pocket filter

Commissioning of the decentralised ventilation units
Commissioning/parameter setting of the decentralised ventilation units without integration into an on-site MCE/BACS
  • Visual inspection of the on-site device connections, for compliance with the respective installation specifications from the installation and configuration instructions: air connections, heating/cooling connection, electrical connections, integration into the installed unit casing, connections of external components
  • Check and, if necessary, adapt the project parameters preset in the factory with regard to customer-specific adaptations
  • Functional test of the individual components (control elements, fans, valves, dampers, sensors)
  • Checking the project-specific control functions, including any special functions such as potential-free switch contacts
  • Documentation of the device settings and service work in a service report. The service report must be signed by your company or a representative as the client
  • Invoicing is based on a flat rate, derived from the number of devices and distance

Commissioning/parameter setting of the decentralised ventilation units with integration into an on-site MCE/BACS
  • Visual inspection of the on-site device connections, for compliance with the respective installation specifications from the installation and configuration instructions: air connections, heating/cooling connection, electrical connections, integration into the installed unit casing, connections of external components, connections of the MCE/BACS
  • Check and, if necessary, adapt the project parameters preset in the factory with regard to customer-specific adaptations
  • Functional test of the individual components (control elements, fans, valves, dampers, sensors)
  • Checking the project-specific control functions, including any special functions such as potential-free switch contacts
  • Functional test of the communication to the MCE/BACS in cooperation with the appointed MCR technology company:
    • Checking that the on-site settings comply with the specifications in the installation and configuration instructions
    • Input test of the data points sent on site
    • Output test of the output data points
    • Trial operation of the operating states that can be switched by the MCE/BACS
  • Documentation of the device settings and service work in a service report. The service report must be signed by your company as the client or by an authorised representative of your company
  • Invoicing is based on a flat rate, derived from the number of devices and distance

Instruction in operation and maintenance
  • One-time instruction for the operation of the decentralised ventilation units consisting of:
    • Description of the device functions on the device, already in operation
    • Description of the room control panel and the room conditions that can be influenced by it
    • Description of the maintenance work
  • Invoicing on a flat-rate basis, carried out by the responsible sales representative
SA-DHV0EH30BBW/3363 × 410 × 1030/0/C3MAT/MT/C/Z/A
|||||||||| ||||||
12345678910 111213141516

1 Type

SA-D Ventilation unit for ceiling installation X-CUBE/ SCHOOLAIR-D

2 Variant

HV High volume flow rate and rotary heat recovery unit

3 Installation situation
0 Installation integrated in suspended ceiling

F freely suspended installation

T partially integrated in suspended ceiling

Z Installation in a pre-assembled frame¹

I Installation situation to be decided²

4 Heat exchanger

EH with electric air heater

5 Heat recovery construction

12 1200 W

18 1800 W

24 2400 W

30 3000 W

6 Construction

BB Outdoor air connection to the rear, exhaust air connection to the rear

LB Outdoor air connection to the left, exhaust air connection to the rear (not with installation situation F or connection W)

BR Outdoor air connection to the rear, exhaust air connection to the right (not with installation situation F or connection W)

LR Outdoor air connection to the left, exhaust air connection to the right (not with installation situation F or connection W)

7 Connection

0 without connection (only with installation situation I)

W Wall connection sealing kit for outdoor air and exhaust air (not with installation situation I)

B Flanged collar (Ø 315 mm) for outdoor air and exhaust air (not with installation situation I)

Q Duct connection (270 × 270 mm) for outdoor air and exhaust air (not with installation situation I)

8 Nominal size [mm]

Width × height × depth

3363 × 410 × 1030 (only with installation situation 0)

3555 × 410 × 1030 (only with installation situation F)

3905 × 410 × 1030 (only with installation situation T)

3900 × 440 × 1099 (only with installation situation Z)

3355 × 410 × 1030 (only with installation situation I)

9 Exposed surface

0 powder-coated, RAL 9010 (pure white), GU 30

P1 powder-coated, RAL 7012 (basalt grey), GU 30 or specify alternative RAL CLASSIC colour, GU 30

10 Control system

OR without control system

C3 with FSL-CONTROL III

11 Control function

MA Master

SL Slave

12 Real time clock

Only with control function MA

No entry: without real time clock

T with real time clock

13 Interface

No entry: without interface

MT with Modbus TCP

MR with Modbus RTU (only with control function MA)

BI with BACnet IP

BM with BACnet MS/TP (only with control function MA)

14 Air quality sensor

Only with control function MA

No entry: without air quality sensor

C with CO2sensor

V with VOC sensor

15 Supply air temperature sensor

Z with supply air temperature sensor

16 Outdoor air temperature sensor

Only with control function MA

No entry: without outdoor air temperature sensor

A with outdoor air temperature sensor

¹ Accessory door frame to be ordered separately

² Basic unit is supplied without accessories. Required accessories must be ordered separately.

Order example: SA-D-HV-0-EH-30-BB-W/3363×410×1030/0/C3-MA-T/MR/C/Z/A

TypeSA-DVentilation unit for ceiling installation X-CUBE/SCHOOLAIR-D
VariantHVHigh volume flow rate and rotary heat recovery unit
Installation situation0Installation integrated in suspended ceiling
Heat exchangerEHwith electric air heater
Heat exchanger construction303000 W
ConstructionBBOutdoor air connection to the rear, exhaust air connection to the rear
ConnectionWWall connection sealing kit for outdoor air and exhaust air
Nominal size [mm]3363×410×1030Width 3363, height 410, depth 1030
Exposed surface0powder-coated, RAL 9010 (pure white)
ControlC3with FSL-CONTROL III
Control functionMAMaster
Real time clockTwith real time clock
InterfaceMRwith Modbus RTU
Air quality sensorCwith CO2sensor
Supply air temperature sensorZwith supply air temperature sensor
Outdoor air temperature sensorAwith outdoor air temperature sensor

Učitavanje

Informacije o proizvodu

Brošure

Sertifikati

production {"x-frame-options"=>"SAMEORIGIN", "x-xss-protection"=>"1; mode=block", "x-content-type-options"=>"nosniff", "x-download-options"=>"noopen", "x-permitted-cross-domain-policies"=>"none", "referrer-policy"=>"strict-origin-when-cross-origin", "strict-transport-security"=>"max-age=31536000; includeSubDomains", "content-type"=>"text/html; charset=utf-8"}

Podeli stranicu

Preporuči ovu stranicu

Preporuči ovu stranicu slanjem linka putem email poruke.

Polja označena sa (*) su obavezna polja.

Podeli stranicu

Zahvaljujemo se na Vašoj preporuci!

Vaša preporuka je poslata i biće uskoro isporučena.

Kontakt

Tu smo za vas

Molimo Vas da navedete sadržinu poruke i vrstu zahteva
Tel.: +381 11 2622 543 | Fax: +49 (0)2845/202-265

Polja označena sa (*) su obavezna polja.

Kontakt

Zahvaljujemo na vašoj poruci!

Vaša poruka je poslata i biće uskoro obrađena.
Naše odeljenje za servisnu podršku će Vas kontaktirati u najkraćem roku.
Za opšta pitanja u vezi proizvoda ili usluga možete takoše da pozovete:
Tel.: +381 11 2622 543 | Fax: +381 11 2624 150

Kontakt

Tu smo za vas

Molimo Vas da navedete sadržinu poruke i vrstu zahteva
Tel.: +381 11 2622 543 | Fax: +49 (0)2845/202-265

Attachment (max. 10MB)

Polja označena sa (*) su obavezna polja.

Kontakt

Zahvaljujemo na vašoj poruci!

Vaša poruka je poslata i biće uskoro obrađena.
Naše odeljenje za servisnu podršku će Vas kontaktirati u najkraćem roku.
Za opšta pitanja u vezi proizvoda ili usluga možete takoše da pozovete:
Tel.: +381 11 2622 543 | Fax: +381 11 2624 150