VME_img_02psd.png
Volume flow rate measuring unit VME with attachment XTS/XTD

 

 

 

 

VME_img_07_BTDpsd.png
Volume flow rate measuring unit VME with control components BTD and BTS

VME with control component BTD

VME with control component BTD

VME_img_05psd.psd.link
Volume flow rate measuring unit VME with control component XTS/XTD

Type VME with control component XTD

VME_img_10psd.png

Type VME with control component ELAB TCU3

VDI6022_gs_01ai.ai.link
Tested to VDI 6022

Tested to VDI 6022

VME_img_02psd.png
VME_img_07_BTDpsd.png
VME_img_05psd.psd.link
VME_img_10psd.png
VDI6022_gs_01ai.ai.link

VME   

For the measurement of volume flow rates in ducts


 

Rectangular volume flow rate measuring unit for recording or monitoring of volume flow rates

  • Manual volume flow rate measuring
  • Continuous volume flow rate measuring
  • Recording of measured values for other controllers or for the LABCONTROL air management system
  • Optional effective pressure transducer for the automatic recording of measured values, factory mounted and complete with wiring and tubing
  • Casing air leakage to EN 15727, up to class D

 

Optional equipment and accessories

  • Surface powder-coated, silver grey (RAL 7001)
  • Dynamic or static effective pressure transducers

 

 

 


General Information

Application

  • Rectangular volume flow rate measuring unit for the manual recording or automatic measuring of volume flow rates
  • Simplified commissioning, approval and maintenance
  • Optional dynamic effective pressure transducer for systems with clean air
  • Optional static effective pressure transducer for systems with contaminated air



Special features

  • Suitable for permanent installation because of low differential pressure
  • High accuracy of volume flow rate measurements



Nominal sizes

  • 39 nominal sizes from 200 × 100 to 1000 × 1000



Construction



  • Galvanised sheet steel
  • P1: Powder-coated, silver grey (RAL 7001)



Parts and characteristics

  • Ready-to-commission unit which consists of mechanical parts and an optional differential pressure transducer.
  • Averaging effective pressure sensor for volume flow rate measurement

 

Only for variant with optional differential pressure transducer as add-on part:

  • Optional differential pressure transducer, factory mounted and wired
  • Aerodynamic functional testing on a special test rig before shipping of each unit
  • Set-up data is given on a label or volume flow rate scale affixed to the unit



Attachments

  • Dynamic effective pressure transducer (BTD, XTD)
  • Static effective pressure transducer (BTS, XTS)
  • LABCONTROL: Components for air management systems



Construction features

  • Rectangular casing
  • Flanges on both ends, suitable for duct connection
  • Connection points for effective pressure measuring tubes with 6 mm inside diameter 



Materials and surfaces

Galvanised sheet steel variant

  • Casing made of galvanised sheet steel
  • Effective pressure sensor made of aluminium

Powder-coated construction (P1)

  • Casing made of galvanised sheet steel, powder-coated
  • Differential pressure sensor made of aluminium profiles with powder coating



Standards and guidelines

Meets the hygiene requirements of

  • EN 16798, Part 3
  • VDI 6022, Sheet 1
  • DIN 1946, Part 4
  • For other applicable standards and guidelines refer to the hygiene certificate

Casing air leakage

  • EN 15727, class D except B+H ≤ 700, class C



Maintenance

  • Maintenance-free as construction and materials are not subject to wear


Tehničke informacije

Function, Technical data, Quick sizing, Specification text, Order code

  • Function
  • TECHNICAL DATA
  • QUICK SIZING
  • SPECIFICATION TEXT
  • ORDER CODE
VME with attachment BTD VME-BTD_gc_01ai.png

1: Effective pressure sensor
2: Transmitter (optional add-on part)
3: Casing


The volume flow rate measuring unit is fitted with an effective pressure sensor for measuring the volume flow rate. The effective pressure recorded with this sensor is either measured and evaluated manually, or transformed into an electrical signal by a measuring transducer (effective pressure transducer).


Nominal sizes200 × 100 – 1000 × 1000 mm
Volume flow rate range42 – 14246 l/s or 149 – 51289 m³/h
Effective pressure rangeapprox. 2 – 260 Pa *
Operating temperature10 to 50 °C
Measurement accuracy±4 – 13% of the measured value
Maximum differential pressure1000 Pa

For more information about quick sizing click here.

Specification text

Rectangular volume flow rate measuring unit for the measurement of volume flow rates in air conditioning systems, available in 39 nominal sizes. For the manual volume flow rate measuring or for the continuous monitoring of the actual value signal. Ready-to-commission unit which consists of the casing with an averaging differential pressure sensor. Differential pressure sensor with 3 mm measuring holes (resistant to dust and pollution). Meets the hygiene requirements of EN 16798, Part 3, VDI 6022, Sheet 1, and DIN 1946, Part 4.
 

Special features

  • Suitable for permanent installation because of low differential pressure
  • High accuracy of volume flow rate measurements


Materials and surfaces

Galvanised sheet steel construction

  • Casing made of galvanised sheet steel
  • Effective pressure sensor made of aluminium 

Powder-coated construction (P1)

  • Casing made of galvanised sheet steel 
  • Surface powder-coated, silver grey (RAL 7001)
  • Effective pressure sensor made of aluminium 



Connection type

  • Flanges on both ends, suitable for duct connection


Technical data


  • Nominal sizes: 200 × 100 to 1000 × 1000 mm
  • Volume flow rate range:  42 – 14246 l/s or 149 – 51289 m³/h
  • Effective pressure range: approx. 2 – 260 Pa 
  • Operating temperature: 10 to 50 °C
  • EN 15727, class D except B+H ≤ 700, class C


VMEP1/600 × 400/XTD/0
|||||
12345
1 Type
VME
Volume flow rate measuring unit, rectangular

2 Material
No entry: galvanised sheet steel
P1 Powder-coated RAL 7001 (silver grey)

3 Nominal size [mm]
Specify size (width × height)

4 Attachment
No entry: without attachment
XTD dynamic effective pressure transducer, analogue, display
BTD dynamic effective pressure transducer, analogue, MP bus, Modbus RTU, BACnet MS/TP
XTS static effective pressure transducer, analogue, display
BTS static effective pressure transducer, analogue, MP bus, Modbus RTU, BACnet MS/TP

5 Signal voltage range
For the actual value signal (required only if an attachment has been selected)
0 0 – 10 V DC
2 2 – 10 V DC


Order example: VME-P1/600x400/XTD/0

TypeVME
MaterialPowder-coated RAL 7001 (silver grey)
Nominal size [mm]Width 600, height 400
AttachmentDynamic differential pressure transducer, analogue, display
Signal voltage range0 – 10 V DC
,
VMEP1/600 × 400/ELAB/ECE0/UMZ
| | | | | | |
1 2 3 4 5 6 7
1 Type
VME
Volume flow rate measuring unit, rectangular

2 Material
No entry: galvanised sheet steel
P1 Powder-coated RAL 7001 (silver grey)

3 Nominal size [mm]
Specify size (width × height)

4 Attachment (control component)
ELAB
EASYLAB TCU3

5 Equipment function
SC
Supply air capture
EC Extract air capture

6 Signal voltage range
For the actual value signal
E0 0 – 10 V DC
E2 2 – 10 V DC

7 Expansion modules
Option 1: Power supply
No entry: 24 V AC/DC
T with EM-TRF for 230 V AC mains supply
U with EM-TRF-USV (including battery pack) for uninterruptible 230 V AC power supply (UPS)

Option 2: Communication interface
No entry: without communication interface
B with EM-BAC-MOD for BACnet MS/TP
M with EM-BAC-MOD for Modbus RTU
I with EM-IP for BACnet IP, Modbus IP and web server
R with EM-IP (including real time clock, RTC) for BACnet IP, Modbus IP and web server

Option 3: Automatic zero point correction
No entry: without automatic zero point adjustment
Z with EM-AUTOZERO solenoid valve for automatic zero point correction


Order example: VME-P1/600×400/ELAB/EC-E0/UMZ

TypeVME
MaterialPowder-coated RAL 7001 (silver grey)
Nominal size [mm]Width 600, height 400
Attachment (control component)EASYLAB TCU3
Equipment functionExtract air capture
Signal voltage range0 – 10 V DC
Expansion modulesPower supply: with EM-TRF UPS (incl. battery) for 230 V AC uninterruptible mains supply (UPS)
Communication interface: with EM-BAC-MOD for Modbus RTU
Automatic zero point adjustment: with EM-AUTOZERO, solenoid valve for automatic zero point adjustment

Variants, Product details, Additional product information

  • Variants
  • PRODUCT DETAILS
  • ADDITIONAL PRODUCT INFORMATION

Installation and commissioning

  • The installation orientation of ELAB must be as shown on the sticker
  • The installation orientation of XTD/XTS or BTD/BTS is not critical


Upstream conditions

The volume flow rate accuracy Δq applies to a straight upstream section of the duct. Bends, junctions or a narrowing or widening of the duct cause turbulence that may affect measurement. Duct connections, e.g. branches off the main duct, must comply with EN 1505. Some installation situations require straight duct sections upstream.



Optional attachments for effective pressure transducers


AttachmentInterfaceEffective pressure transducerManufacturer
Differential pressure transducer, dynamic
XTD0 – 10 V or 2 – 10 Vintegrated
BTD0 - 10 V or 2 - 10 V or MP-Bus or Modbus RTU or BACnet MS/TPintegrated
Differential pressure transducer, static
XTS0 – 10 V or 2 – 10 Vintegrated
BTS0 - 10 V or 2 - 10 V or MP-Bus or Modbus RTU or BACnet MS/TPintegrated
ELAB

TROX plug and play communication system and 0 - 10 V or 2 - 10 V or with optional accessories: Modbus, BACnet, web server

integrated

① TROX/Gruner, ② TROX/Belimo, ③ TROX

Učitavanje

Informacije o proizvodu

Sertifikati

Uputstva za rukovanje

production {"X-Frame-Options"=>"SAMEORIGIN", "X-XSS-Protection"=>"1; mode=block", "X-Content-Type-Options"=>"nosniff", "X-Download-Options"=>"noopen", "X-Permitted-Cross-Domain-Policies"=>"none", "Referrer-Policy"=>"strict-origin-when-cross-origin", "Content-Security-Policy"=>"frame-ancestors 'self' https://api.scrivito.com https://punchoutcommerce.com https://www.trox.de https://trox-extern.com https://psp40.onventis.com https://psp22.onventis.com https://trox4u.troxgroup.com", "Strict-Transport-Security"=>"max-age=31536000; includeSubDomains", "Content-Type"=>"text/html; charset=utf-8"}

Podeli stranicu

Preporuči ovu stranicu

Preporuči ovu stranicu slanjem linka putem email poruke.

Polja označena sa (*) su obavezna polja.

Podeli stranicu

Zahvaljujemo se na Vašoj preporuci!

Vaša preporuka je poslata i biće uskoro isporučena.

Kontakt

Tu smo za vas

Molimo Vas da navedete sadržinu poruke i vrstu zahteva
Tel.: +381 11 2622 543 | Fax: +49 (0)2845/202-265

Polja označena sa (*) su obavezna polja.

Kontakt

Zahvaljujemo na vašoj poruci!

Vaša poruka je poslata i biće uskoro obrađena.
Naše odeljenje za servisnu podršku će Vas kontaktirati u najkraćem roku.
Za opšta pitanja u vezi proizvoda ili usluga možete takoše da pozovete:
Tel.: +381 11 2622 543 | Fax: +381 11 2624 150

Kontakt

Tu smo za vas

Molimo Vas da navedete sadržinu poruke i vrstu zahteva
Tel.: +381 11 2622 543 | Fax: +49 (0)2845/202-265

Attachment (max. 10MB)

Polja označena sa (*) su obavezna polja.

Kontakt

Zahvaljujemo na vašoj poruci!

Vaša poruka je poslata i biće uskoro obrađena.
Naše odeljenje za servisnu podršku će Vas kontaktirati u najkraćem roku.
Za opšta pitanja u vezi proizvoda ili usluga možete takoše da pozovete:
Tel.: +381 11 2622 543 | Fax: +381 11 2624 150