Application
Special characteristics
Nominal sizes
Variants
Construction
Parts and characteristics
Attachments
Useful additions
Construction features
Material and surfaces
Galvanised sheet steel
Powder-coated construction (P1)
Standards and guidelines
Meets the hygiene requirements of
Casing air leakage
Closed damper blade air leakage:
NS 200 × 100, NS 300 × 100, NS 200 × 200
NS 300 × 200, NS 400 × 200, NS 500 × 200, NS 600 × 200
Maintenance
Functional description
The damper blade works as a control element and as a differential pressure sensor. Through the differential pressure duct in the shaft, the detected differential pressure reaches the transducer (static or dynamic), and is converted into an electrical signal and compared with the setpoint value. In case of a control deviation, the integrated actuator changes the position of the damper blade. Thereby, the volume flow rate is kept constant in close tolerances over the entire differential pressure range.
Nominal sizes |
|
Volume flow rate range | 16 - 960 l/s or 58 - 3456 m³/h |
Volume flow rate control range (controller with dynamic differential pressure measurements) | approx. 10 - 100 % of the nominal volume flow rate |
Minimum differential pressure | up to 50 Pa (without secondary silencer) |
Maximum differential pressure | Control component with dynamic transducer: 900 Pa, Control component with static transducer: 600 Pa |
Operating temperature | 10 to 50 °C |
Quick sizing tables provide a good overview of the minimum pressure differences, the volume flow accuracy Δqv and the expected sound pressure levels in the room. Intermediate values may be achieved by interpolation. The sound power levels for calculating the sound pressure levels were measured in the TROX laboratory according to DIN EN ISO 5135 - see "Basic information and nomenclature". Precise results and spectral data for all control components can be obtained by using our Easy Product Finder design programme. The nominal size is initially selected according to the given volume flow rates qvmin and qvmax.
Volume flow rate ranges and minimum differential pressure values
The minimum differential pressure of VAV terminal units is an important factor in designing the ductwork and in rating the fan including speed control. It must be ensured that for all operating conditions and for all terminal units, a sufficient differential pressure is applied to each controller (Δpstmin). The measurement point(s) for fan speed control must be selected accordingly. The volume flow rate range for VAV terminal units depends on the nominal size and on the control component (attachment) used.
Volume flow rate ranges and minimum differential pressure
Controller for dynamic and static measuring principle
Attachment: Easy, XB0, XM0, XM0-J6, XS0, XS0-J6, XDMB0, XSMB0
B | H | qv [l/s] | qv [m³/h] | Δpstmin [Pa] | Δqv [±%] | |
---|---|---|---|---|---|---|
(1) | (2) | |||||
200 | 100 | 16 | 58 | 1 | 3 | 18 |
200 | 100 | 64 | 230 | 8 | 33 | 8 |
200 | 100 | 112 | 403 | 25 | 101 | 6 |
200 | 100 | 160 | 576 | 50 | 204 | 5 |
300 | 100 | 25 | 87 | 1 | 3 | 18 |
300 | 100 | 96 | 346 | 8 | 33 | 8 |
300 | 100 | 168 | 605 | 24 | 100 | 6 |
300 | 100 | 240 | 864 | 48 | 202 | 5 |
200 | 200 | 33 | 116 | 1 | 2 | 18 |
200 | 200 | 128 | 461 | 6 | 22 | 8 |
200 | 200 | 224 | 806 | 18 | 66 | 6 |
200 | 200 | 320 | 1152 | 37 | 133 | 5 |
300 | 200 | 48 | 173 | 1 | 2 | 18 |
300 | 200 | 192 | 691 | 6 | 22 | 8 |
300 | 200 | 336 | 1210 | 17 | 65 | 6 |
300 | 200 | 480 | 1728 | 35 | 131 | 5 |
400 | 200 | 65 | 231 | 1 | 2 | 18 |
400 | 200 | 256 | 922 | 6 | 22 | 8 |
400 | 200 | 448 | 1613 | 17 | 65 | 6 |
400 | 200 | 640 | 2304 | 34 | 130 | 5 |
500 | 200 | 80 | 288 | 1 | 2 | 18 |
500 | 200 | 320 | 1152 | 6 | 22 | 8 |
500 | 200 | 560 | 2016 | 16 | 64 | 6 |
500 | 200 | 800 | 2880 | 33 | 129 | 5 |
600 | 200 | 96 | 346 | 1 | 2 | 18 |
600 | 200 | 384 | 1382 | 6 | 22 | 8 |
600 | 200 | 672 | 2419 | 16 | 64 | 6 |
600 | 200 | 960 | 3456 | 33 | 129 | 5 |
(1) Basic unit
(2) Basic unit with secondary silencer TX
Quick sizing table for sound pressure levels
The quick sizing tables include common sound insulation and attenuation values. If the sound pressure level is above the permissible value, a larger air terminal unit and/or a silencer or acoustic cladding are required. For more information on the acoustic data, see Basic Information and Nomenclature.
Quick sizing table for air-regenerated noise LPA
Controller including silencer variants
B | H | qv [l/s] | qv [m³/h] | 150 Pa | 500 Pa | ||
---|---|---|---|---|---|---|---|
(1) | (2) | (1) | (2) | ||||
200 | 100 | 16 | 58 | 31 | 15 | 40 | 22 |
200 | 100 | 64 | 230 | 40 | 25 | 49 | 32 |
200 | 100 | 112 | 403 | 44 | 29 | 52 | 36 |
200 | 100 | 160 | 576 | 48 | n. V. | 54 | 39 |
300 | 100 | 25 | 87 | 25 | 10 | 36 | 18 |
300 | 100 | 96 | 346 | 37 | 23 | 48 | 32 |
300 | 100 | 168 | 605 | 42 | 30 | 52 | 36 |
300 | 100 | 240 | 864 | 46 | n. V. | 54 | 39 |
200 | 200 | 33 | 116 | 32 | 19 | 42 | 27 |
200 | 200 | 128 | 461 | 42 | 29 | 52 | 37 |
200 | 200 | 224 | 806 | 44 | 30 | 53 | 39 |
200 | 200 | 320 | 1152 | 45 | 30 | 54 | 40 |
300 | 200 | 48 | 173 | 35 | 19 | 47 | 30 |
300 | 200 | 192 | 691 | 44 | 27 | 55 | 38 |
300 | 200 | 336 | 1210 | 45 | 28 | 57 | 39 |
300 | 200 | 480 | 1728 | 46 | 30 | 58 | 39 |
400 | 200 | 65 | 231 | 31 | 17 | 43 | 27 |
400 | 200 | 256 | 922 | 38 | 24 | 50 | 35 |
400 | 200 | 448 | 1613 | 39 | 26 | 51 | 37 |
400 | 200 | 640 | 2304 | 40 | 29 | 52 | 38 |
500 | 200 | 80 | 288 | 33 | 15 | 44 | 26 |
500 | 200 | 320 | 1152 | 40 | 24 | 51 | 34 |
500 | 200 | 560 | 2016 | 42 | 26 | 53 | 36 |
500 | 200 | 800 | 2880 | 43 | 29 | 54 | 38 |
600 | 200 | 96 | 346 | 32 | 17 | 44 | 27 |
600 | 200 | 384 | 1382 | 38 | 24 | 50 | 34 |
600 | 200 | 672 | 2419 | 40 | 25 | 51 | 36 |
600 | 200 | 960 | 3456 | 41 | 29 | 52 | 37 |
(1) Basic unit
(2) Basic unit with secondary silencer TX
n.a.: Specified static differencial pressure Δpst is smaller than minimum differential pressure Δpstmin.
Quick sizing table for case-radiated noise LPA
B | H | qv [l/s] | qv [m³/h] | 150 Pa | 500 Pa |
---|---|---|---|---|---|
(1) | |||||
200 | 100 | 16 | 58 | 18 | 26 |
200 | 100 | 64 | 230 | 27 | 35 |
200 | 100 | 112 | 403 | 30 | 39 |
200 | 100 | 160 | 576 | 35 | 41 |
300 | 100 | 24 | 87 | 13 | 24 |
300 | 100 | 96 | 346 | 26 | 36 |
300 | 100 | 168 | 605 | 31 | 41 |
300 | 100 | 240 | 864 | 37 | 45 |
200 | 200 | 32 | 116 | 20 | 29 |
200 | 200 | 128 | 461 | 30 | 39 |
200 | 200 | 224 | 806 | 34 | 43 |
200 | 200 | 320 | 1152 | 36 | 46 |
300 | 200 | 48 | 173 | 24 | 36 |
300 | 200 | 192 | 691 | 34 | 46 |
300 | 200 | 336 | 1210 | 38 | 50 |
300 | 200 | 480 | 1728 | 40 | 52 |
400 | 200 | 64 | 231 | 19 | 31 |
400 | 200 | 256 | 922 | 29 | 41 |
400 | 200 | 448 | 1613 | 33 | 45 |
400 | 200 | 640 | 2304 | 35 | 47 |
500 | 200 | 80 | 288 | 20 | 31 |
500 | 200 | 320 | 1152 | 31 | 42 |
500 | 200 | 560 | 2016 | 35 | 46 |
500 | 200 | 800 | 2880 | 38 | 49 |
600 | 200 | 96 | 346 | 19 | 31 |
600 | 200 | 384 | 1382 | 29 | 41 |
600 | 200 | 672 | 2419 | 33 | 45 |
600 | 200 | 960 | 3456 | 36 | 48 |
(1) Basic unit
Specification text
VAV terminal units in rectangular design for variable and constant volume flow systems, for supply air or extract air, in several nominal sizes. High control accuracy of set volume flow rates, even in unfavourable upstream conditions. Control range at least 1:10. Differential pressure measurement and control via damper blade. Tubeless differential pressure transmission through differential pressure duct in shaft Closed blade air leakage according to EN 1751: class 2 or 3 depending on nominal size. Casing air leakage according to EN 1751, class C Ready-to-commission unit which consists of the mechanical parts and the factory mounted electronic control component. Position of the damper blade indicated externally at the control component. The damper blade is factory set to open position, which allows a ventilation airflow even without control. Meets the hygiene requirements of EN 16798, Part 3, of VDI 6022, Sheet 1, and of DIN 1946, Part 4.
Special characteristics
Materials and surfaces
Equivalence criteria
Connection type
Technical data
Maximum differential pressure
Closed blade air leakage, class 2 or 3 depending on nominal size.
Specification text attachment
Variable volume flow control with electronic Easy controller for applying a reference value and capturing an actual value to be integrated with the central BMS.
Life cycle assessment
A life cycle assessment is available for the product series in form of an Environmental Product Declaration (EPD) that has been checked and published by a programme holder.
TVE-Q | / | 300 × 200 | / | Easy |
| | | | | | ||
1 | 3 | 5 |
Order example: TVE-Q/300×200/Easy
Type | TVE-Q |
Nominal size [mm] | Width 300, height 200 |
Attachments (control component) | Volume flow controller, dynamic, analogue interface, setting of qvmin and qvmax with potentiometers provided by others |
Order code for volume flow control (with VARYCONTROL attachment)
TVE-Q | – | P1 | / | 300 × 200 | / | XB0 | / | V | 0 | / | 200 – 900 [m³/h] |
| | | | | | | | | | | | | | |||||
1 | 3 | 4 | 5 | 6 | 7 | 8 |
Order example: TVE-Q-P1/500×200/XB0/V0/850-2200[m³/h]
Type | TVE-Q |
Material | Air duct powder-coated RAL 7001, silver grey |
Nominal size [mm] | Width 500, height 200 |
Attachments (control component) | Volume flow controller, dynamic, analogue interface |
Operating mode | Variable operation |
Signal voltage range | 0 – 10 V DC |
Operating values for factory setting | 850 – 2200 [m³/h] |
Installation and commissioning
TVE-Q control components VARYCONTROL
Attachment | Controlled variable | Interface | Effective pressure transducer | Actuator | Manufacturer |
---|---|---|---|---|---|
Easy controller, dynamic | |||||
Easy | qv | 0 – 10 V | integrated | Slow running integrated | (1) |
Compact controller, dynamic | |||||
XB0 | qv | 0 – 10 V or 2 – 10 V | integrated | Slow running integrated | (1) |
XM0 | qv | 0 - 10 V or 2 - 10 V or | integrated | Slow running integrated | (1) |
XM0–J6 | qv | Modbus RTU interface with RJ12 socket (for X-AIRCONTROL) | integrated | Slow running integrated | (1) |
XDMB0 | qv | 0 - 10 V or 2 - 10 V or Modbus RTU or BACnet MS/TP | integrated | Slow running integrated | (1) |
Compact controller, static | |||||
XS0 | qv | Modbus RTU interface | integrated | Slow running integrated | (1) |
XS0–J6 | qv | Modbus RTU interface with RJ12 socket (for X-AIRCONTROL) | integrated | Slow running integrated | (1) |
XSMB0 | qv | 0 – 10 V or 2 – 10 V or Modbus RTU or BACnet MS/TP | integrated | Slow running, integrated | (1) |
qv Volume flow rate
(1) TROX
Podeli stranicu
Preporuči ovu stranicu
Preporuči ovu stranicu slanjem linka putem email poruke.
Podeli stranicu
Zahvaljujemo se na Vašoj preporuci!
Vaša preporuka je poslata i biće uskoro isporučena.
Kontakt
Tu smo za vas
Molimo Vas da navedete sadržinu poruke i vrstu zahteva
Tel.: +381 11 2622 543 | Fax: +49 (0)2845/202-265
Kontakt
Zahvaljujemo na vašoj poruci!
Vaša poruka je poslata i biće uskoro obrađena.
Naše odeljenje za servisnu podršku će Vas kontaktirati u najkraćem roku.
Za opšta pitanja u vezi proizvoda ili usluga možete takoše da pozovete:
Tel.: +381 11 2622 543 | Fax: +381 11 2624 150
Kontakt
Tu smo za vas
Molimo Vas da navedete sadržinu poruke i vrstu zahteva
Tel.: +381 11 2622 543 | Fax: +49 (0)2845/202-265
Kontakt
Zahvaljujemo na vašoj poruci!
Vaša poruka je poslata i biće uskoro obrađena.
Naše odeljenje za servisnu podršku će Vas kontaktirati u najkraćem roku.
Za opšta pitanja u vezi proizvoda ili usluga možete takoše da pozovete:
Tel.: +381 11 2622 543 | Fax: +381 11 2624 150